| Notes |
| Date |
Text |
| 2002-02-05 00:00:00 | *******************UNSAT!*************** | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION AND RESUBMIT. | | | | | | 1) A.I.C. RATING AT FIRST MEANS OF | | | DISCONNECT,ALL UNITS. | | | | | | 2) "A" & "B" UNITS CONFORM TO 230-3. | | | | | | 3) BATH ROOMS TO COMPLY WITH | | | 210-52D.INCLUDE SAME IN PANEL SCHEDULES | | | AND LOAD CALCULATIONS. | | | | | | 4) GROUND LEVEL UNITS COMPLY WITH | | | 210-52E. | | | | | | 5)CONDENSING UNITS GFCI,210-63 NEC & | | | 309.2 MECH. | | | | | | 6)UNIT "D" BED ROOMS 2&3 AND UNIT "C" | | | BED ROOM #3 TO COMPLY WITH NFPA-72 | | | 2-2.1.1.1. | | | | | | 7) ALL WIRING TO CONFORM TO THE FAIR | | | HOUSING ACT,CHAPTER#524 CFR 100-205. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | (561) 659-8096 | | | EXT.8392 |
|