2002-02-05 00:00:00*******************UNSAT!***************
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION AND RESUBMIT.
  
 1) A.I.C. RATING AT FIRST MEANS OF
 DISCONNECT,ALL UNITS.
  
 2) "A" & "B" UNITS CONFORM TO 230-3.
  
 3) BATH ROOMS TO COMPLY WITH
 210-52D.INCLUDE SAME IN PANEL SCHEDULES
 AND LOAD CALCULATIONS.
  
 4) GROUND LEVEL UNITS COMPLY WITH
 210-52E.
  
 5)CONDENSING UNITS GFCI,210-63 NEC &
 309.2 MECH.
  
 6)UNIT "D" BED ROOMS 2&3 AND UNIT "C"
 BED ROOM #3 TO COMPLY WITH NFPA-72
 2-2.1.1.1.
  
 7) ALL WIRING TO CONFORM TO THE FAIR
 HOUSING ACT,CHAPTER#524 CFR 100-205.
  