| 2002-01-15 00:00:00 | ******************* UNSAT ************** |
| | |
| | 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS |
| | PER 220-3-C-1 FOR MORETHAN 500SQ FT. |
| | PLEASE NOTE THAT A NEW ELECTRICAL PANEL |
| | IS SHOWN IN NEW ADDITION, BUT NO RISER |
| | DIAGRAM WAS SUBMITTED FOR REVIEW. |
| | PLEASE SUBMIT A RISER DIAGRAM SHOWING |
| | WHERE/HOW THIS PANEL IS BEING FED. |
| | WIRE SIZES/CONDUIT ECT. |
| | |
| | 2) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S) PER 210-11-C-3. |
| | MUST BE 20A AND #12AWG. |
| | PLEASE SUBMIT A PANEL SCHEDULE SHOWING |
| | EXSITING? NEW? CIRCUITS, REQ`D. |
| | |
| | 3)NOTE: PLEASE NOTE THAT MORETHAN 50% OF |
| | THE ELECTRICAL IS BEING DONE, NOTE SD`S |
| | WILL BE REQ`D INSIDE AND OUTSIDE ANY |
| | EXISTING BEDROOMS. PLEASE SHOW |
| | PLEASE NOTE SD REQ`D IN CABANA, THIS |
| | ROOM HAS CLOSET/STORAGE AND IS |
| | CONSIDERED AN ADAPTABLE BEDROOM. NFPA-72 |
| | 2-1.1.1 |
| | |
| | 4)NOTE: PLEASE NOTE THAT IF ANY NEW |
| | ELECTRICAL SERVICE IS GOING TO BE |
| | SUBMITTED FOR REVIEW, PLEASE SUBMIT THE |
| | AIC RATINGS FOR ANY NEW SERVICE. 110-9 |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW, IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |