| Plan Review Notes For Permit 01121260 |
| Permit Number |
01121260 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2002-02-26 00:00:00 | DENIED | | | REFERENCE: SPC-94-FACBC-97 | | | | | | 1) ALL COMMENTS FROM PREVIOUS REVIEW | | | HAVE NOT BEEN ADDRESSED (1 THRU 4) OR | | | NOT ADDRESSED PROPERLY #5. | | | 2) FROM PREVIOUS REVIEWS - UNDERSINK | | | GREASE TRAP IS NOT APPROVED WEATHER OR | | | NOT THE GREASE TRAP IS WAIVED. SHT P-1 | | | 3) SHT P-1 SEPARATE GREASE LINE SHALL BE | | | INSTALLED SO THE SAMPLE POINT CAN BE | | | MONITERED BEFORE TYING INTO THE SANITARY | | | 4) IF AN EMERGENCY PAN IS INSTALLED ON | | | A WATER HEATER THAN IT SHALL HAVE A | | | DRAIN LINE INSTALLED. SPC SEC 507.8.2 | | | 5) SUBMIT AN EXISTING FLOOR PLAN FOR | | | DEMO. DEMO PERMIT REQUIRED | | | 6) SHT P-1 RPZ BACKFLOW REQUIRED ON | | | WATER SERVICE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|