Plan Review Notes
Plan Review Notes For Permit 01121260
Permit Number 01121260
Review Stop P
Sequence Number 2
Notes
Date Text
2002-02-12 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) FROM PREVIOUS PLAN REVIEW #2, UNDER
 SINK GREASE TRAP IS NOT APPROVED. MINIM-
 UM SIZE GREASE TRAP IS 750 GAL.
 2) SHT P-1 SEPARATE GREASY WASTE LINE
 SHALL BE INSTALLED. TO MONITOR SAMPLE
 POINT, SAMPLE POINT SHALL BE INSTALLED
 PRIOR TO TYING GREASE LINE TO SANITARY.
 3) FROM PREVIOUS PLAN REVIEW #8, 1"
 DRAIN LINE IS REQUIRED FOR EMERGENCY PAN
 4) FROM PREVIOUS PLAN REVIEW #10, PLEASE
 SUBMIT AN EXISTING FLOOR PLAN FOR DEMO.
 EXISTING FIXTURES NEED TO BE SHOWN SO
 INSPECTORS CAN SEE IF THEY ARE CAPPED
 PROPERLY DURING DEMO INSPECTIONS. PLUMB.
 DEMO PERMIT REQUIRED.
 5) SHT P-1 RPZ BACKFLOW REQUIRED ON
 WATER SERVICE. (NEW COMMENT)
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377