| Plan Review Notes For Permit 01121260 |
| Permit Number |
01121260 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-02-12 00:00:00 | DENIED | | | REFERENCE: SPC-94-FACBC-97 | | | | | | 1) FROM PREVIOUS PLAN REVIEW #2, UNDER | | | SINK GREASE TRAP IS NOT APPROVED. MINIM- | | | UM SIZE GREASE TRAP IS 750 GAL. | | | 2) SHT P-1 SEPARATE GREASY WASTE LINE | | | SHALL BE INSTALLED. TO MONITOR SAMPLE | | | POINT, SAMPLE POINT SHALL BE INSTALLED | | | PRIOR TO TYING GREASE LINE TO SANITARY. | | | 3) FROM PREVIOUS PLAN REVIEW #8, 1" | | | DRAIN LINE IS REQUIRED FOR EMERGENCY PAN | | | 4) FROM PREVIOUS PLAN REVIEW #10, PLEASE | | | SUBMIT AN EXISTING FLOOR PLAN FOR DEMO. | | | EXISTING FIXTURES NEED TO BE SHOWN SO | | | INSPECTORS CAN SEE IF THEY ARE CAPPED | | | PROPERLY DURING DEMO INSPECTIONS. PLUMB. | | | DEMO PERMIT REQUIRED. | | | 5) SHT P-1 RPZ BACKFLOW REQUIRED ON | | | WATER SERVICE. (NEW COMMENT) | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|