| 2002-02-14 00:00:00 | *******************DENIED*************** | | | | | | | | | 1.PROVIDE OUTSIDE AIR CALCULATIONS AS | | | PER ASHRAE 62-89. | | | | | | 2.PROVIDE AIR BALANCE SCHEDULE SHOWING | | | COMPLIANCE WITH 1997 SMC 501.2. | | | | | | 3.INDICATE CONDENSATE TERMINATION. | | | | | | PLEASE NOTE, SEPARATE PERMIT REQUIRED | | | FOR HOOD, FIRE SUPRESSION, AND WALKIN | | | COOLERS.PROVIDE PLANS AND | | | MANUFACTURERS SUBMITTAL DATA WITH | | | PERMIT APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|