Plan Review Notes
Plan Review Notes For Permit 01121260
Permit Number 01121260
Review Stop P
Sequence Number 1
Notes
Date Text
2002-01-12 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) COVER PAGE, CODE REVIEW SHOULD READ
 SBCCI SPC-94
 2) PLANS TO BE ROUTED TO DEPT OF BUSIN-
 ESS HOTEL & RESTURANT DIVISION FOR PLAN
 REVIEW BEFORE RESUBMITTING.
 3) GREASE TRAP TO BE SIZED AND LOCATED
 BY UTILITY DEPT REGONIAL WASTE WATER
 TREATMENT. PLEASE CALL RODNEY COMPO
 (561) 837-4074 - WASTE ORD. #2938-96
 4) SHT P-1 UNDER SINK GREASE TRAP DETAIL
 NOT APPROVED.
 5) SHT P-1 GREASY WASTE SHALL BE SEPAR-
 ATETED FROM SANITARY.
 6) SHT P-1 FLOOR SINK REQUIRED FOR IN-
 DIRECT WASTE FROM WATER HEATER. SEC 804
 7) SHT P-1 CONDENSATE TO FLOOR SINK NOT
 FLOOR DRAIN. SPC SEC 804.5
 8) SHT P-1 WATER HEATER DETAIL, PLUMBING
 KEYNOTE #2. HEATER PAN NOT REQUIRED, BUT
 IF USED A 1" PAN DRAIN IS REQUIRED. SPC
 SEC 507.8.2
 9) SHT P-1 WATER HAMMER ARRESTORS SHALL
 BE LOCATED BY FIXTURES IN AN "EFFECTIVE
 RANGE", NOT AT TOP OF DROPS AS SHOWN.
 10) PLEASE SUBMIT A SHEET SHOWING DEMO
 OF EXISTING SPACE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377