| Plan Review Notes For Permit 01121260 |
| Permit Number |
01121260 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-01-12 00:00:00 | DENIED | | | REFERENCE: SPC-94-FACBC-97 | | | | | | 1) COVER PAGE, CODE REVIEW SHOULD READ | | | SBCCI SPC-94 | | | 2) PLANS TO BE ROUTED TO DEPT OF BUSIN- | | | ESS HOTEL & RESTURANT DIVISION FOR PLAN | | | REVIEW BEFORE RESUBMITTING. | | | 3) GREASE TRAP TO BE SIZED AND LOCATED | | | BY UTILITY DEPT REGONIAL WASTE WATER | | | TREATMENT. PLEASE CALL RODNEY COMPO | | | (561) 837-4074 - WASTE ORD. #2938-96 | | | 4) SHT P-1 UNDER SINK GREASE TRAP DETAIL | | | NOT APPROVED. | | | 5) SHT P-1 GREASY WASTE SHALL BE SEPAR- | | | ATETED FROM SANITARY. | | | 6) SHT P-1 FLOOR SINK REQUIRED FOR IN- | | | DIRECT WASTE FROM WATER HEATER. SEC 804 | | | 7) SHT P-1 CONDENSATE TO FLOOR SINK NOT | | | FLOOR DRAIN. SPC SEC 804.5 | | | 8) SHT P-1 WATER HEATER DETAIL, PLUMBING | | | KEYNOTE #2. HEATER PAN NOT REQUIRED, BUT | | | IF USED A 1" PAN DRAIN IS REQUIRED. SPC | | | SEC 507.8.2 | | | 9) SHT P-1 WATER HAMMER ARRESTORS SHALL | | | BE LOCATED BY FIXTURES IN AN "EFFECTIVE | | | RANGE", NOT AT TOP OF DROPS AS SHOWN. | | | 10) PLEASE SUBMIT A SHEET SHOWING DEMO | | | OF EXISTING SPACE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|