Plan Review Notes
Plan Review Notes For Permit 01121260
Permit Number 01121260
Review Stop M
Sequence Number 1
Notes
Date Text
2001-12-20 00:00:00********************DENIED**************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW.
  
 1.OUTSIDE AIR CALCULATIONS AS PER
 ASHRAE 62-1989.
  
 2.CONDENSATE SHALL TERMINATE TO EITHER
 AN APPROVED DRYWELL OR TO STORM
 DRAINAGE SYSTEM AS PER COUNTYWIDE
 AMENDMENTS 1994 SPC 804.3.
  
 PLEASE NOTE ADDITIONAL PERMITS REQUIRED
 FOR HOOD, FIRE SUPRESSION AND WALK-IN
 COOLER/FREEZER.PROVIDE PLANS WITH
 PERMIT APPLICATION.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.