Plan Review Notes
Plan Review Notes For Permit 01121260
Permit Number 01121260
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-12-27 00:00:001) WRONG BUILDING CODE REFERENCED ON
 THE PLANS.
 2) A DISCREPANCY EXISTS BETWEEN THE
 OCCUPANT LOAD LISTED AND THE FURNITURE
 LAYOUT. THERE ARE MORE THAN 18 SEATS
 PROVIDED ON THE FURNITURE LAYOUT. PLEASE
 CORRECT INFORMATION.
 3) NO INTERIOR FINISH CLASSIFICATION
 INFORMATION PROVIDED WITH PLANS FOR
 THE WALLS AND CEILINGS.
 4) EXITING WIDTH CACULATION INCORRECT.
 5) SEPARATE PLANS AND PERMITS REQUIRED
 FOR THE HOOD,DUCT AND FIRE SUPPRESSION
 SYSTEM PLANNED FOR USE.
 6) PLEASE INDICATE ON THE PLANS THE
 TENANT SEPARATION DEMISING WALLS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910