| Plan Review Notes For Permit 01121260 |
| Permit Number |
01121260 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-12-27 00:00:00 | 1) WRONG BUILDING CODE REFERENCED ON | | | THE PLANS. | | | 2) A DISCREPANCY EXISTS BETWEEN THE | | | OCCUPANT LOAD LISTED AND THE FURNITURE | | | LAYOUT. THERE ARE MORE THAN 18 SEATS | | | PROVIDED ON THE FURNITURE LAYOUT. PLEASE | | | CORRECT INFORMATION. | | | 3) NO INTERIOR FINISH CLASSIFICATION | | | INFORMATION PROVIDED WITH PLANS FOR | | | THE WALLS AND CEILINGS. | | | 4) EXITING WIDTH CACULATION INCORRECT. | | | 5) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR THE HOOD,DUCT AND FIRE SUPPRESSION | | | SYSTEM PLANNED FOR USE. | | | 6) PLEASE INDICATE ON THE PLANS THE | | | TENANT SEPARATION DEMISING WALLS. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|