Plan Review Notes For Permit 01121260
Permit Number 01121260
Review Stop E
Sequence Number 1
Notes
Date Text
2001-12-28 00:00:00****************** UNSAT ***********
  
 1)NOTE: PLEASE NOTE THAT THE NOTES ON
 PLANS MENTION "96" NEC AND PLANS
 NOTES MENTION A "97" NEC ?? PLEASE NOTE
 THAT THERE IS NOT A 97 NEC AND WE ARE
 CURRENTLY UNDER THE "99" NEC. PLEASE
 CORRECT.
  
 2)NOTE: PLEASE NOTE THAT COLOR CODING
 FOR FEEDERS (277/480) MUST BE BROWN,
 PURPLE, YELLOW.
 215-8
  
 3)NOTE: PLEASE NOTE THAT ALL AIC RATINGS
 ARE TO BE SUBMITTED BY THE ENGINEER OF
 RECORD.
  
 PLEASE MAKE THE ABOVE CORRECTIONS AND
 SUBMIT FOR REVIEW. IF THERE ARE ANY
 QUESTIONS, PLEASE CALL.
  