| 2002-01-03 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT # 01121260 |
| | 3111 45TH STRET |
| | PLAN REVIEW |
| | QUIZUOS SUBS |
| | CONTACT STEVE JOHNSON |
| | TEL (954) 557-2177 |
| | |
| | 1)- COVER SHEET,CODE REVIEW: NOT THE |
| | 1999 SOUTH FLORIDA BUILDING CODE, |
| | PLANS SUBMITTED FOR PLAN REVIEW AS OF |
| | DEC. 18,2001 WILL BE REVIEWED UNDER |
| | THE 1997 STANDARD BUILDING CODE. PLANS |
| | SUBMITTED FOR PERMIT APPLICATION FROM |
| | JAN 1/2002 THROUGH FEBRUARY 28/2002 |
| | MAY BE REVIEWED UNDER EITHER THE 1997 |
| | STANDARD BUILDING CODE OR THE 2001 |
| | FLORIDA CODE. THE DESIGNER OF RECORD |
| | SHALL BE REQUIRED TO IDENTIFY WHICH CODE |
| | WAS USED IN DEVELOPING THE PROJECT. |
| | PLANS SUBMITTED FOR PERMIT APPLICATION |
| | AFTER MARCH 1ST/ 2002 SHALL BE REVIEWED |
| | UNDER THE 2001 FLORIDA CODE. |
| | |
| | 2)- SBC 1003.1.2. OCCUPANT LOAD, |
| | DISCREPANCY: THE COVER SHEET INDICATES A |
| | OCC. LOAD FOR THE DINING ROOM OF 16 VS. |
| | THE FLOOR PLAN OF 22. |
| | |
| | 3)- FL ACCESSIBILITY CODE 5.1. WHEERE |
| | FIXED TABLES ARE PROVIDED, AT LEAST 5% |
| | BUT NOT LESS THAN ONE, OF THE FIXED |
| | TABLES( OR A PORTION OF THE DINING |
| | COUNTER) SHALL BE ACCESSIBLE & SHALL |
| | COMPLY WITH 4.32. |
| | |
| | 4)- SHEET # 2: |
| | A) INDICATES A SECTION 4/C A UL LIST- |
| | ING U-419, FOR A NONBEARING WALL EITHER |
| | 1-4 HR. RATING. WHAT OCCUPANCIES ARE ON |
| | EACH SIDE OF THIS PROPOSED OCCUPANCY? |
| | THIS WILL BE THE DETERMINING FACTOR AS |
| | TO THE OCCUPANCY SEPERATION. SBC |
| | TABLE 704.1.WHAT TYPE OF ROOF DECK ABOVE |
| | B) NOTE FOR SOLID BACKING IN TENANT |
| | SEPERATION WALLS, SEE SECTION 707.1 |
| | COMBUSTIBLES IN CONCEALED SPACES. |
| | C) NOTE "ALANCE ABOVE SHEET 5 OF 5": |
| | DETAILS DO NOT SPECIFY THE SIZE OF THE |
| | ALL THREAD, NOTE PAGE 5 INDICATES |
| | SECURE STRUCTURE, VERIFY INSTALLATION, |
| | WHO? |
| | |
| | 5)- SHEET 4 INDICATES INTERIOR FINISHES |
| | BUT THERE IS NO INFORMATION AS TO SBC |
| | TABLE 803.3 MINIMUM INTERIOR FINISH |
| | CLASSIFICATION. FLAMESPREAD/ SMOKE |
| | DEVELOPMENT. |
| | |
| | 6)- SHEET 4 HARDWARE NOTES INDICATES THE |
| | USE OF THE "UNIFORM BUILDING CODE" THE |
| | SECTION SHOULD BE FROM SBC 1997, SEC. |
| | 1020.2.(1). |
| | |
| | 7)- SHEET M-1 ROOF TOP UNITS, ATTACHMENT |
| | MAKES REFRENCE TO BLDG. STRUCTURAL PLANS |
| | FOR ADDITIONAL INFORMATION? MISSING? |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561)659-8096X8412 |