Plan Review Notes
Plan Review Notes For Permit 01121260
Permit Number 01121260
Review Stop B
Sequence Number 1
Notes
Date Text
2002-01-03 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01121260
 3111 45TH STRET
 PLAN REVIEW
 QUIZUOS SUBS
 CONTACT STEVE JOHNSON
 TEL (954) 557-2177
  
 1)- COVER SHEET,CODE REVIEW: NOT THE
 1999 SOUTH FLORIDA BUILDING CODE,
 PLANS SUBMITTED FOR PLAN REVIEW AS OF
 DEC. 18,2001 WILL BE REVIEWED UNDER
 THE 1997 STANDARD BUILDING CODE. PLANS
 SUBMITTED FOR PERMIT APPLICATION FROM
 JAN 1/2002 THROUGH FEBRUARY 28/2002
 MAY BE REVIEWED UNDER EITHER THE 1997
 STANDARD BUILDING CODE OR THE 2001
 FLORIDA CODE. THE DESIGNER OF RECORD
 SHALL BE REQUIRED TO IDENTIFY WHICH CODE
 WAS USED IN DEVELOPING THE PROJECT.
 PLANS SUBMITTED FOR PERMIT APPLICATION
 AFTER MARCH 1ST/ 2002 SHALL BE REVIEWED
 UNDER THE 2001 FLORIDA CODE.
  
 2)- SBC 1003.1.2. OCCUPANT LOAD,
 DISCREPANCY: THE COVER SHEET INDICATES A
 OCC. LOAD FOR THE DINING ROOM OF 16 VS.
 THE FLOOR PLAN OF 22.
  
 3)- FL ACCESSIBILITY CODE 5.1. WHEERE
 FIXED TABLES ARE PROVIDED, AT LEAST 5%
 BUT NOT LESS THAN ONE, OF THE FIXED
 TABLES( OR A PORTION OF THE DINING
 COUNTER) SHALL BE ACCESSIBLE & SHALL
 COMPLY WITH 4.32.
  
 4)- SHEET # 2:
 A) INDICATES A SECTION 4/C A UL LIST-
 ING U-419, FOR A NONBEARING WALL EITHER
 1-4 HR. RATING. WHAT OCCUPANCIES ARE ON
 EACH SIDE OF THIS PROPOSED OCCUPANCY?
 THIS WILL BE THE DETERMINING FACTOR AS
 TO THE OCCUPANCY SEPERATION. SBC
 TABLE 704.1.WHAT TYPE OF ROOF DECK ABOVE
 B) NOTE FOR SOLID BACKING IN TENANT
 SEPERATION WALLS, SEE SECTION 707.1
 COMBUSTIBLES IN CONCEALED SPACES.
 C) NOTE "ALANCE ABOVE SHEET 5 OF 5":
 DETAILS DO NOT SPECIFY THE SIZE OF THE
 ALL THREAD, NOTE PAGE 5 INDICATES
 SECURE STRUCTURE, VERIFY INSTALLATION,
 WHO?
  
 5)- SHEET 4 INDICATES INTERIOR FINISHES
 BUT THERE IS NO INFORMATION AS TO SBC
 TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION. FLAMESPREAD/ SMOKE
 DEVELOPMENT.
  
 6)- SHEET 4 HARDWARE NOTES INDICATES THE
 USE OF THE "UNIFORM BUILDING CODE" THE
 SECTION SHOULD BE FROM SBC 1997, SEC.
 1020.2.(1).
  
 7)- SHEET M-1 ROOF TOP UNITS, ATTACHMENT
 MAKES REFRENCE TO BLDG. STRUCTURAL PLANS
 FOR ADDITIONAL INFORMATION? MISSING?
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096X8412