| Plan Review Notes For Permit 01121259 |
| Permit Number |
01121259 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2002-05-16 00:00:00 | *************** UNSAT *************** | | | | | | 1 )NOTE: PLEASE NOTE THAT THE LOAD | | | CALCULATIONS NEED TO BE SHOWN. SQ FT/ | | | RECEPT LOADS ETC. PER 220-3,220-10, | | | 220-11, 220-13. (215-5) | | | PLEASE SHOW TRACK LIGHTING PER 220-12B | | | PLEASE ALSO NOTE ALL CONTINUOUS LOADS | | | ARE TO BE SHOWN AT 125%. | | | | | | 2)NOTE: PLEASE SHOW ALL BRANCH CIRCUIT | | | #`S ON PLANS AND CORRELATE WITH PANEL | | | SCHEDULES SUBMITTED. USE HAS CHANGED . | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-806 EXT 8372 |
|