Plan Review Notes
Plan Review Notes For Permit 01121249
Permit Number 01121249
Review Stop B
Sequence Number 1
Notes
Date Text
2002-01-15 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 SBC = STANDARD BUILDING CODE
 SBC*= STANDARD BUILD'G CODE (AMENDMENTS)
 FL ACC CODE = FLORIDA ACCESSIBILITY CODE
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SBC* 104.2.3 SEALED PLANS.
 SHEET 2 OF 2 SHALL BE SIGNED AND SEALED.
  
 3) SBC 704.1.1OCCUPANCY SEPARATION.
 THE DAY CARE CENTER SHALL BE SEPARATED
 FROM THE REMAINDER OF THE BUILDING BY
 CONSTRUCTION WITH A FIRE RESISTANCE
 RATING OF 2 HOURS.DOORS IN THIS
 CONSTRUCTION SHALL HAVE A MINIMUM FIRE
 RESISTANCE RATING OF 1 1/2 HOURS
  
 4) FL ACC CODE 4.1.6(1)(B) AND 4.1.2(1)
 AT LEAST ONE ACCESSSIBLE ROUTE TO THE
 FACILITY ENTRANCE SHALL BE INDICATED ON
 THE PLANS.
  
 5) FL ACC CODE 4.1.6(2)AN ACCESSIBLE
 ENTRANCE, ACCESSIBLE ROUTE, ACCESSIBLE
 RESTROOM AND ACCESSIBLE DRINKING
 FOUNTAIN SHALL BE PROVIDED.REVISE
 PLANS TO DEMONSTRATE COMPLIANCE.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUERIES PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499