Plan Review Notes
Plan Review Notes For Permit 01121162
Permit Number 01121162
Review Stop P
Sequence Number 1
Notes
Date Text
2002-01-10 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) PLANS SHALL BE ROUTED TO PALM BEACH
 COUNTY HEALTH UNIT DIVISION OF ENVIRON-
 MENTAL HEALTH, 901 EVERNIA WPB 33401,
 (561) 355-3018 EXT 1194 BEFORE RESUB-
 MITTING PLANS FOR PLUMBING REVIEW.
 2) PLEASE SUPPLY CALCULATIONS FOR MINI-
 MUM FACILITIES PER SPC SEC 407 AND TABLE
 407.
 3) SHT A-2/A-7 PLEASE SHOW CLEAR FLOOR
 SPACE FOR HDCP FIXTURES IN RMS #105A,
 106A, AND 107 PER FACBC SEC 4.2.4.1,
 AND SEC'S 4.16.2, 4.18.3, 4.19.3.
 4) SHT A-2/A-7 TURNING RADIUS TO BE
 SHOWN IN TOILET ROOM NOT STALL FOR MENS
 AND WOMENS RESTROOMS. SEE FIG 30(E)
 5) SHT A-7 DETAIL #4 W/C TO BE 18" NOT
 18"MIN. LAV TO BE MINIMUM OF 15" TO C/L
 OFF WALL NOT 18" FROM WALL TO SIDE OF
 LAV AS SHOWN.
 6) SHT P-1 FD-2 FUNNEL FLOOR DRAIN NOT
 APPROVED. ALL INDIRECT WASTE TO FLOOR
 SINK. SPC SEC 804.
 7) SHT P-2 KITCHEN EQUIP. PLBG NOTES #3
 ALL INDIRECT WASTE TO FLOOR SINK NOT
 FLOOR DRAINS. SPC SEC 804
 8) SHT P-2 CONDENSATE SHALL DRAIN TO
 STORM OR DRYWELL NOT SANITARY AS SHOWN.
 UTILITY ORD. ALSO CUT SHEETS FOR EACH
 AIR HANDLER IS REQUIRED SHOWING CONDEN-
 SATE DRAIN SIZE. SHOW DETAIL FOR DRYWELL
 9) SHT P-2 CAN WASH SHALL BE PIPED TO
 GREASY WASTE NOT SANITARY.
 10) SHT P-2 GREASE TRAP TO BE SIZED AND
 LOCATED BY WASTE TREATMENT AND ENVIRON-
 MENTAL SERVICES. PLEASE CONTACT R. COMPO
 (561) 837-4074. WASTE ORD. #2938-96
 11) SHT P-2 DRY VENT ON GREASY WASTE NOT
 PER CODE. (COL LINE 1 BETWEEN COL'S E &
 F & BY DISHWASHER) SPC SEC 906.2.1
 12) SHT P-2 FLOOR SINKS IN DRY FOOD
 STORAGE AREA TO BE FLOOR DRAINS AND
 SHALL HAVE TRAP PRIMERS.
 13) SHT P-3 RPZ BACKFLOW REQUIRED ON
 WATER SERVICE FOR THIS BLDG.
 14) SHT P-3 PLUMBING DRAWING NOTES #3 &
 SHT P-4 WATER RISER DIAGRAM, WATER HAMM-
 ER ARRESTORS SHALL BE LOCATED CLOSE TO
 FIXTURES IN "AN EFFECTIVE RANGE" NOT AT
 THE TOP OF DROPS AS STATED OR SHOWN.
 REF. PDI-WH 201 AND MANUFACTURE INSTALLA
 TION INSTRUCTIONS.
 15) SHTS P-2 & P-4 DISHWASHER SHALL BE
 DISCHARGED INTO SANITARY NOT GREASE LINE
 PER UTILITY ORD.
 16) SHT P-4 VENT GOOSENECK FOR GREASE
 TRAP NOT APPROVED. PLEASE VENT GREASE
 LINE IN WALL AS IT ENTERS THE BLDG.
 17) SHT P-4 2 WAY CLEAN OUTS REQUIRED ON
 INLET AND DISCHARGE SIDES OF GREASE TRAP
 18) SHT P-4 CONDENSATE TO VENT THRU ROOF
 SEPARATELY FROM SANITARY. NO CROSS CON-
 NECTION OF SYSTEMS.
 19) SHT P-5 GREASE TRAP DETAIL NOT APP-
 ROVED. SEE ATTACHED SHEET FOR APPROVED
 GREASE TRAP.
 20) SHT P-5 WATER HEATER DETAIL, P&T
 AND PAN DRAIN TO BE PIPED SEPARATELY
 SPC SEC 507.8.4.-PAN AND RELIEF LINE
 TO DISCHARGE INDIRECTLY INTO A FLOOR
 SINK NOT FLOOR DRAIN. SPC SEC 804 AND
 SHALL HAVE A TRAP PRIMER.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377