| 2001-12-27 00:00:00 | ****************DENIED****************** | | | 1. PROVIDE REQUIRED VENTILATION FOR HAY | | | STORAGE ROOM | | | 2. PROVIDE AIR BALANCE SCHEDULE SHOWING | | | COMPLIANCE W/ SMC 501.2 | | | 3. PROVIDE OUTSIDE AIR CALCULATIONS | | | SHOWING COMPLIANCE WITH ASHRAE 62-89 | | | 4. ROOF MOUNTED EQUIPMENT MOUNTED HIGHER | | | THAN 20 FOOT ABOVE FINISHED GRADE SHALL | | | REQUIRE A PERMENANT MEANS OF ACCESS TO | | | THE ROOF | | | 5. ROOF SLOPE ON MECHANICAL PLANS | | | APPEARS GREATER THAN 4:12. IF SO | | | COMPLIANCE WITH SMC 304.6.2 WILL BE | | | REQUIRED | | | 6. SEPARATE PLANS AND PERMITS WILL BE RE | | | QUIRED FOR WALK IN COOLER/FREEZER, KITCH | | | EN HOOD AND SUPPRESSION SYSTEM. |
|