| Plan Review Notes For Permit 01121162 |
| Permit Number |
01121162 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-12-27 00:00:00 | 1) WRONG EDITION OF THE LIFE SAFETY | | | CODE REFERENCED. SHOULD READ 1985 | | | EDITION INSTEAD OF 1997 EDITION. | | | 2) NO HYDRAULIC CALCULATIONS PROVIDED | | | WITH FIRE SPRINKLER DRAWINGS.ALSO NO | | | PIPE SIZES OR HANGER LOCATIONS PROVIDED. | | | 3) A KNOX-BOX RAPID ENTRY SYSTEM WILL | | | BE REQUIRED. | | | 4) PLEASE EXPLAIN WELDING AREA 102. | | | PLEASE REVIEW NFPA 51B WITH REGARDS | | | TO WELDING AND CUTTING OPERATIONS. | | | 5) IT APPEARS THAT EXITING TAKES PLACE | | | THRU CARPENTRY,SHOP,AND WELDING. THIS | | | IS NOT ALLOWED. | | | 6) PLEASE EXPLAIN FIRE ALARM SEQUENCE | | | OF OPERATION NOTES"RELEASE DOOR HOLDS | | | AND ELECTRIC LOCKS". | | | 7) PROVIDE SEPARATE PLANS AND PERMITS | | | FOR HOOD,DUCT, FIRE SUPPRESSION AND | | | FIRE ALARM SYSTEM. | | | 8) KITCHEN EXHAUST FAN DISPLAYS 700 CFM. | | | A MINIMUM OF 1500 AIR VELOCITY IS | | | REQUIRED. | | | 9) BUILDING ADDRESS IS REQUIRED. | | | 10) PROVIDE UL NUMBERS FOR RATED WALLS. | | | 11) PLEASE PROVIDE PRODUCT APPROVAL FOR | | | COILING DOOR 120B. | | | 12) NO SMOKING OR OPEN FLAME SIGNS WILL | | | BE REQUIRED IN HAY ROOM. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|