2001-12-27 00:00:001) WRONG EDITION OF THE LIFE SAFETY
 CODE REFERENCED. SHOULD READ 1985
 EDITION INSTEAD OF 1997 EDITION.
 2) NO HYDRAULIC CALCULATIONS PROVIDED
 WITH FIRE SPRINKLER DRAWINGS.ALSO NO
 PIPE SIZES OR HANGER LOCATIONS PROVIDED.
 3) A KNOX-BOX RAPID ENTRY SYSTEM WILL
 BE REQUIRED.
 4) PLEASE EXPLAIN WELDING AREA 102.
 PLEASE REVIEW NFPA 51B WITH REGARDS
 TO WELDING AND CUTTING OPERATIONS.
 5) IT APPEARS THAT EXITING TAKES PLACE
 THRU CARPENTRY,SHOP,AND WELDING. THIS
 IS NOT ALLOWED.
 6) PLEASE EXPLAIN FIRE ALARM SEQUENCE
 OF OPERATION NOTES"RELEASE DOOR HOLDS
 AND ELECTRIC LOCKS".
 7) PROVIDE SEPARATE PLANS AND PERMITS
 FOR HOOD,DUCT, FIRE SUPPRESSION AND
 FIRE ALARM SYSTEM.
 8) KITCHEN EXHAUST FAN DISPLAYS 700 CFM.
 A MINIMUM OF 1500 AIR VELOCITY IS
 REQUIRED.
 9) BUILDING ADDRESS IS REQUIRED.
 10) PROVIDE UL NUMBERS FOR RATED WALLS.
 11) PLEASE PROVIDE PRODUCT APPROVAL FOR
 COILING DOOR 120B.
 12) NO SMOKING OR OPEN FLAME SIGNS WILL
 BE REQUIRED IN HAY ROOM.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910