| Plan Review Notes For Permit 01121162 |
| Permit Number |
01121162 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-12-31 00:00:00 | ******************* UNSAT ************* | | | | | | 1)NOTE: PLEASE NOTE THAT E-1 SHOWS | | | 3-SET-S OF PIPE AND NOTES ON E-2 | | | MENTIONS | | | ONLY 2 SETS?PLEASE CORRELATE. | | | | | | 2)NOTE: PLEASE NOTE THAT E-1 SHOWS 800A | | | GOING TO PANEL "P-2", PLEASE SEE E-6, | | | "P-2" IS SHOWN AT 600A? PLEASE CORRELATE | | | WHICH ONE IT WILL BE. WIRE RATED FOR | | | 800A`S. | | | | | | 3)NOTE: PLEASE NOTE THAT LOAD | | | CALCULATIONS NEED TO BE SHOWN. PLEASE | | | SHOW WATTS/ PER SQ FT, OUTLETS AT 180VA | | | ETC ETC. | | | PLEASE SHOW ALL CONTINUOUS LOADS AT | | | 125%EVERYTHING IS SHOWN AT CONNECTED | | | LOAD. 220-13,230-42,215-2/3,220-3, ETC. | | | | | | 4)NOTE: PLEASE NOTE LARGEST MOTOR LOADS | | | AT 125% ALSO. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS. | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | 561-659-8096 EXT 8372 |
|