2002-01-05 00:00:00BUILDING PLAN REVIEW
 PERMIT # 10021162
 1301 SUMMIT BLVD
 CONT: PCL CONSTRUCTION
 TEL: (407)363-0059
  
 SBC= 1997 STANDARD BUILDING CODE
 SBC*= AMENDMENTS STANDARD BUILDING CODE
 FL ACC= 1997 FLORIDA ACCESSIBILITY CODE
  
 1)- PERMIT APPLICATION INDICATES STEEL
 STRUCTURE TO BE A PRE- ENGINEERED BUILD-
 ING. SBC 2203.1 THE DESIGN, FABRICATION
 AND ERECTION OF STRUCTURAL STEEL BUILD-
 INGS SHALL CONFORM TO THE REQUIREMENTS
 OF EITHER AISC SPECIFICATIONS FOR STRUC-
 TURAL BUILDINGS - ALOWABLE STRESS DESIGN
 OR THE AISC LOAD AND RESISTANCE FACTOR
 DESIGN SPECIFICATION FOR STRUCTURAL
 STEEL BUILDINGS.
 APROFESSIONAL ENGINEER SHALL SIGN HIS NA
 ME AND AFFIX HIS SEAL TO ALL PLANS ,
 SPECIFICATIONS, REPORTS, OR OTHER DOCUME
 NTS PREPAREDOR ISSUED BY SAID REGIS-
 TRAUNT AND BEING FILED FOR PUBLIC
 DOCUMENT. THERE IS NO STRUCTURAL ENGINE-
 ERING PLANS FOR THE PRE-ENGINEERED
 STRUCTURE.
 IF THIS IS A BUILDING (MODULAR)WAS APP-R
 OVED BY THE DEPARTMENT OF COMMUNITY
 AFFAIRS, THERE WOULD ALSO BE ENGINEERED
 PLANS.
 2)- SBC 1804.2.7.2(3) SOILS REPORT
 INDICATING THE BEARING VALUE.
 3)- BLOCK INFILL WALLS INDICATE OPENINGS
 SBC 1606.2.6.2 COMPONENTS & CLADDING
 SHALL REQUIRE (2 COPIES) OF PRODUCT
 APPROVAL REPORTS FOR ALL GLAZED OPENINGS
 SWING DOORS, OVERHEAD DOORS, SKYLIGHT
 ETC. EITHER SBCCI OR DADE COUNTY PRODUCT
 REPORTS ARE ACCEPTED.
 4)- INDICATE THE POS/ NEG PRESURE FOR
 EACH OF THE OPENINGS, INCLUDING END ZONE
 5)- MEZZANINE: SEE 503.2.3 FOR AREA OF
 MEZZANINE, ONLY 1/3 OF THE SQ FT OR 420
 SQ FT ALLOWABLE, PLANS INDICATE 549 S F
 SEE ATTACHMENT, ALSO MEZZANINE USEAGE
 ISNOT LISTED. IF NOT STORAGE, VERTICAL
 ACCESSIBILITYSHALL BE A CONCERN.
 6)- PLANS DO NOT INDICATE DOOR NOR
 WINDOW BUCK ATTACHMENT?
 7)- SBC104.2.2 ADDITIONAL INFORMATION
 REQUIRED, SHEET A-2 INDICATES A SIDEWALK
 AND HANDICAPPED ENTRY RAMP TO THE PARKI
 NG AREA, WHEN VIEWED ON ELEVATION SHEET
 A-4 IT CUTS THE HANDICAPPED RAMP OFF
 TOTALLY?
 8)- ADD INFO FOR DOCK LEVELER FOR HAY
 ROOM.
 9)- DETAIL FOR RATED WALLS, UL LISTING
 AND HOW WILL A FIRESTOP SYSTEM SEAL
 AGAINST THE METAL ROOF. SBC 705.5.1.2
 REQUIRES A MINIMUM POSITIVE PRESSURE DIF
 FERENTIAL OF 0.01 INCH OF WATER AND
 SHALL HAVE AN F RATING NOT LESS THAN THE
 RATING OF THE WALL.
 BUILDING PLAN REVIEW