| Plan Review Notes For Permit 01120931 |
| Permit Number |
01120931 |
|
| Review Stop |
FS |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-12-13 00:00:00 | 1) IT APPEARS THAT THE FDC IS LOCATED | | | BETWEEN THE POST INDICATOR VALVE AND | | | THE DCDA. THE FDC SHALL HAVE NO SHUT OFF | | | VALVES BETWEEN IT AND THE SYSTEM. | | | 2) THE POST INDICATOR VALVE SHOWN | | | ON THE SYSTEM REQUIRES SUPERVISION. | | | 3) THE UNDERGROUND FIRE LINE IS TO BE | | | INSTALLED IN ACCORDANCE WITH NFPA 24. | | | ALL FIRE PROTECTION SYSTEM PIPING IS | | | TO BE PRESSURE TESTED FOR TWO HOURS | | | AT 200 PSI. | | | 4) PLEASE PROVIDE CUT-SHEETS FOR FIRE | | | SPRINKLER HEADS PLANNED FOR USE. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|