Plan Review Notes
Plan Review Notes For Permit 01120931
Permit Number 01120931
Review Stop FS
Sequence Number 1
Notes
Date Text
2001-12-13 00:00:001) IT APPEARS THAT THE FDC IS LOCATED
 BETWEEN THE POST INDICATOR VALVE AND
 THE DCDA. THE FDC SHALL HAVE NO SHUT OFF
 VALVES BETWEEN IT AND THE SYSTEM.
 2) THE POST INDICATOR VALVE SHOWN
 ON THE SYSTEM REQUIRES SUPERVISION.
 3) THE UNDERGROUND FIRE LINE IS TO BE
 INSTALLED IN ACCORDANCE WITH NFPA 24.
 ALL FIRE PROTECTION SYSTEM PIPING IS
 TO BE PRESSURE TESTED FOR TWO HOURS
 AT 200 PSI.
 4) PLEASE PROVIDE CUT-SHEETS FOR FIRE
 SPRINKLER HEADS PLANNED FOR USE.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910