| Plan Review Notes For Permit 01120926 |
| Permit Number |
01120926 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-12-18 00:00:00 | *************** UNSAT *************** | | | | | | 1)NOTE: PLEASE NOTE NO MAIN DISCONNECT | | | SHOWN AT DETACHED STRUCTURE.ART 225-31 | | | | | | 2)NOTE: PLEASE NOTE EASEMENT ISSUE STILL | | | NEEDS TO BE RESOLVED. | | | | | | 3)NOTE: PLEASE NOTE THAT RISER DIAGRAM | | | IS SHOWN COMING FROM PANEL THAT FEEDS | | | COMMON STREET LIGHTING, PLEASE ALSO | | | NOTE THAT SERVICE IS SUPPOSED TO BE | | | COMING FROM A NEW SEPARATE METER FROM | | | FPL, FROM ELEC ROOM IN "A" BLOCK/?? | | | PLEASE CLARIFY | | | | | | 4)NOTE: PLEASE CLARIFY 4-2/0`S IS | | | ONE OF THESE A GROUNDING CONDUCTOR? | | | PLEASE CLARIFY TRANSFORMER GROUND? | | | 250-30 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 | | | | | | BILL STAPLES | | | ASST BUILDING OFFICIAL | | | 659-8096 EXT 8315 | | | FOR ANY EASEMENT QUESTIONS. |
|