| Plan Review Notes For Permit 01120918 |
| Permit Number |
01120918 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-03-08 00:00:00 | *************** UNSAT ***************** | | | | | | PLEASE NOTE THAT NOTES 1,2,3 FROM FIRST | | | REVIEW WERE NOT DONE. | | | | | | 1)NOTE: PLEASE NOTE THAT NOTE#1 HAS | | | 2/0`S FOR 250AMP SERVICE? PLEASE NOTE | | | THAT WHEN PLANS CAME BACK, THE CONDUCTOR | | | SIZE WENT EVEN SMALLER, DOWN TO 1/0`S? | | | PLEASE NOTE THAT CONDUCTORS ARE TO BE | | | SIZED PER NEC 310-15/16. | | | 310-15, 250A SERVICE IS A MIN OF 4/0`S. | | | | | | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | PLEASE NOTE THAT THIS IS REQ`D AT TIME | | | OF REVIEW OF PLANS. 110-9/215-5. | | | | | | 3)NOTE: PLEASE NOTE THAT RISER STILL | | | DOES NOT SHOWN AN EQUIPMENT GROUNDING | | | CONDUCTOR BETWEEN MAIN DISCONNECT AND | | | PANEL. 250-122. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. ONCE AGAIN, PLEASE CALL IF THERE | | | ARE ANY QUESTIONS,OR GOING OVER THE PLAN | | | -S WOULD BE BETTER SUITED. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|