| Plan Review Notes For Permit 01120918 |
| Permit Number |
01120918 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-12-29 00:00:00 | DENIED; | | | 1.SHOW EXISTING BUILDING DRAIN (SIZE) | | | AND LOCATION. ALSO WHERE NEW PLUMBING | | | WILL TIE INTO. | | | 2.RISER DIAGRAM ARE NOT TO CODE; | | | 2ND FL. WATER CLOSET FLUSHES PAST | | | THE BIDET. | | | ATTIC BATH 3" MIN. PIPE REQUIRED | | | FOR A WATER CLOSET. | | | 3.LAUNDRY AND MECH ROOMS MAYBE TOO SMALL | | | FOR GAS APPLIANCES. SEE "CONFINED | | | SPACE" IN THE 97 SMC CHAPTER 2. USE | | | FOURMULA OF 50 CU. FT. PER 1000 BTU"S | | | TO FIND AREA REQUIRED. VENTS MY BE | | | REQUIRED. | | | 4.A SEPORATE GAS PERMIT IS REQUIRED. GAS | | | CONTRACTOR TO SUBMIT PLANS WITH PERMIT | | | APPLICATION. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT. 8369 |
|