| Plan Review Notes For Permit 01120918 |
| Permit Number |
01120918 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-12-24 00:00:00 | ************* **** UNSAT *************** | | | | | | 1)NOTE: PLEASE NOTE SERVICE MAIN IS | | | SHOWN AT 225A WITH 250A MAIN??? AND | | | WIRE FOR 200AMPS 310-15/310-16 | | | | | | 2)NOTE: PLEASE NOTE MISSING EQUIPMENT | | | GROUNDING CONDCUTOR 250-122 | | | BETWEEN MAIN AND PANEL. | | | | | | 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 4) PLEASE NOTE MISSING OUTLET(S) REQ`D | | | BY 210-52E OF THE NEC. | | | | | | 5) NOTE: PLEASE SHOW ALL OUTLETS SERVING | | | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- | | | -ED PER 210-8-A-6. | | | | | | 6) NOTE: PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S) PER 210-11-C-3. | | | MUST BE 20A AND #12AWG. | | | | | | 7)NOTE: PLEASE CLARIFY GFI PROTECTION | | | FOR SCREENED PORCH RECEPTS. | | | | | | PLEASE SUBMIT ALL OF THE ABOVE INFORMAT- | | | -ION FOR REVIEW. IF THERE ARE ANY | | | QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|