| 2002-01-07 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT# 01120918 |
| | 727 SUNSET RD. |
| | CONT.: ROGER G. THOMAS |
| | TEL: (561)575-1389 |
| | |
| | SBC= 1997 STANDARD BUILDING CODE |
| | SBC*= AMENDMENTS/ STANDARD BUILDING CODE |
| | |
| | 1)- NOTICE OF COMMENCEMENT MUST BE RE- |
| | CORDED AT THE COUNTY COURTHOUSE BEFORE |
| | THE PERMIT MAY BE ISSUED. |
| | |
| | 2)- SBC 1804.2.7.2 SOILS TEST TO VERIFY |
| | THE MINIMUM SAFE BEARING VALUE. |
| | |
| | 3)- ADDITIONAL INFORMATION REQUIRED: |
| | AVERAGE EAVE HEIGTH= |
| | BASIC PRESSURE= |
| | SHEET A-2 MISSING THIS INFORMATION. THE |
| | PRESSURE ZONES FOR ALL EXTERIOR OPENINGS |
| | (WINDOWS & DOORS) SHOW ON ELEVATIONS. |
| | |
| | 4)-MISSING ENERGY CALCS, |
| | |
| | 5)- SHEET A-4 DEPICTS A THIRD STORY, |
| | ATTIC LOFT AND FUTURE BATH, THIS WOULD |
| | REQUIRE THIS STRUCTURE TO BE A TYPE VI |
| | 1-HOUR PROTECTED BUILDING. |
| | A) TABLE 600 TYPE V1 PROTECTED INDICATE |
| | THE 1 HR PROTECTION FOR ALL STRUCTUR |
| | AL MEMBERS AS REQUIRED BY TABLE 600. |
| | B) GIVE A CUT SECTION THROUGH THE 3 |
| | FLOORS INDICATING THE HEIGTH OF EACH |
| | STORY, SBC 1203.2.1 OCCUPLIABLE ROOMS |
| | AND HABITABLE SPACES SHALL NOT HAVE A |
| | CEIL LESS THAN 7'-6", STORAGE, BATHROOMS |
| | MAY BE 7'-0". IF ANY ROOM IN A BUILDING |
| | HAS A SLOPING CEILING, THE PRESCRIBED |
| | CEILING HEIGTH FOR THE ROOM IS REQUIRED |
| | IN ONLY 1/2 THE AREA THEREOF.(1203.2.2) |
| | 6) SHEET A-6 |
| | DISCREPANCY BETWEEN FLOOR PLAN NEW |
| | WINDOWS AND SHEETS 5/SHEET6. IN REVIEW- |
| | ING PLANS WITH HISTORICS THEY INDICATE |
| | THAT NEITHER DRAWING IS CORRECT BUT |
| | CASEMENT WINDOWS SHALL BE INSTALLED? |
| | |
| | 7) SHEET A-5 INDICATES WINDOWS WITH MULL |
| | ION, WINDOW REPORT INDICATES THAT THIS |
| | REPORT IS FOR SINGLE UNIT APPLICATION. |
| | REPORT REQUIRED FOR MULLION. |
| | |
| | 8) FRENCH DOOR REPORT SHALL REQUIRE |
| | LARGE MISSLE IMPACT RESISTANCE PROTEC- |
| | TION. |
| | |
| | 9) SHEET A-11 THE FIRST FLOOR FRAMING |
| | PLAN INDICATES A DOUBLE 2X12 BEAM AROUND |
| | THE PERIMETER OF THE PORCH, WHAT TYPE |
| | OF SUPPORT IS USED WHERE WOOD BEAM ENDS |
| | AT WALL LINE? SECTION OF KITCHEN WHERE |
| | WALL WAS REMOVED, WHAT TYPE OF CONNEC- |
| | TION IS TO BE USED FOR 6X6 POST AND FOR |
| | GIRDER, DOES THE EXISTING 2ND FLOOR |
| | JOIST BEAR ON THIS WALL? |
| | |
| | 10)- SHEET A-7 SECTION 2 STORY INDICATES |
| | STUCCO ALL THE WAY TO THE GROUND, A 6" |
| | AIR GAP REQUIRED TERMITE PROTECTION, |
| | SBC2304.2.5 AMENDMENTS. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561)659-8096X8412 |