2001-12-28 00:00:00************BUILDING PROVISO************
  
 SBC 104.2.2
  
 1. STRUCTURE IS LOCATED IN AN "A8" FLOOD
 ZONE. A FLOOD ELEVATION CERTIFICATE WILL
 BE REQUIRED BEFORE C/O.
  
 2. PRODUCT APPROVALS FOR WINDOWS &
 SLIDING GLASS DOORS ARE EXPIRED.SUBMIT
 UP DATED APPROVALS.
  
 3. SHEET S-1 FOUNDATION NOTES STATE
 SOIL BEARING TO BE 2000 PSF.SHOULD BE
 2500 PSF. CORRECT DRAWINGS & DESIGN
 CERTIFICATION FORM & RESUBMIT.
  
 4. NEED SOIL REPORT
  
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 659-8096 EXT. 8394