| 2003-06-11 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 01120694 | | | ADD: 2901 TUXEDO DRIVE | | | CONTRACTOR: E. O. KOCH | | | CONTACT: H P TOMPKINS | | | TEL: (561)998-0955 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | SUBMITTAL:DENIED | | | | | | 1) FROM THE LAST REVIEW, THE REQUEST FOR | | | SITE SPECIFIC ENGINEERING USING THE CITY | | | FORM WAS NOT ADHERRED TO. 2ND IT IS SITE | | | SPECIFIC REQUIRING A ADDRESS THE COVER | | | SHEET HAS JOBSITE ADDRESS BUT NOT THE | | | DETAIL SHEET D-408764. | | | | | | THE DESIGN PROFESSIONAL FOR THE SITE. | | | EITHERTHE ENGINEER FOR AMERICAN | | | BUILDING COMPANY (JUDSON D. SMITH, P.E.) | | | OR H.P. TOMPKINSWHO DESIGNED THE FOUNDAT | | | ION, SIGN AND SEAL A LETTER ATTESTING | | | THAT THE SITE SPECIFIC ENGINEERING SUP- | | | PLIED BY OVERHEAD DOOR CO.(D-408764) | | | WILL MEET THE POSITIVE & NEGATIVE WIND | | | PRESSURES THAT WILL OCCUR ON THESE | | | OPENINGS. | | | | | | SINCE WE HAVE RECEIVED A PRODUCT TESTING | | | REPORT, THIS REPORT INDICATES THE USE OF | | | GLAZING, REQUIRING STORM SHUTTERS. PRO- | | | VIDE ADDITIONAL INFORMATION ON LARGE | | | MISSLE IMPACT RESISTANT GLAZING OR STORM | | | SHUTTERS. | | | | | | THE FINAL COMMENT IS THIS DOOR SYSTEM | | | IS NOT COVERED UNDER THIS PERMIT. | | | A SEPERATE PERMIT WILL BE REQUIRED SINCE | | | PRODUCT TESETING WAAS NOT PART OF THE | | | ORIGINAL PERMIT PACKAGE. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561)805-6715 |
|