| Plan Review Notes For Permit 01120694 |
| Permit Number |
01120694 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-06-17 00:00:00 | DENIED | | | REFERENCE: SPC-94-FACBC-97 | | | | | | A) COMMENTS FROM LAST REVIEW NOT ADD- | | | RESSED. | | | 1) WILL THERE BE A WATER SERVICE TO THE | | | BLDG? | | | 2) SUBMIT CALCULATIONS FOR MINIMUM FAC- | | | ILITIES PER TABLE 407 | | | 3) BACKFLOW REQUIRED ON WATER SERVICE. | | | 4) N/A | | | 5) SHT CE-1 OF 1 SHT L-1 OF 1 SHOW AN LP | | | TANK (GAS). BUT UN-NUMBERED SHEET AFTER | | | SHT L-1 OF 1 SHOWS NATURAL GAS METER. | | | PLEASE CLAIRFY. | | | 6) GAS PERMIT REQUIRED. PLEASE SEE ATT- | | | ACHED GAS PERMIT APPLICATION REQUIREMENT | | | SHEET FOR INFORMATION REQUIRED FOR GAS | | | PERMIT TO BE ISSUED. | | | 7) IRRIGATION PERMIT REQUIRED. SUBMIT | | | PLANS WITH IRRIGATION PERMIT APPLICATION | | | PLUMBING CONTRACTOR SHALL INSTALL BACK- | | | FLOW FOR IRRIGATION. | | | 8) PLEASE NOTE THAT ALL SHEETS THAT ARE | | | SIGNED AND SEALED SHALL HAVE A TITLE | | | BLOCK CONTAINING PRINTED NAME, ADDRESS, | | | AND NUMBER OF ENGINEER OR ENGNEERING | | | BUSINESS ON THEM PER FS61G15-23.002 | | | 9) PLEASE ADDRESS ALL COMMENTS WITH A | | | REPLY TO EXPEDITE PLAN REVIEW. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|