| 2002-01-02 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT # 01120694 |
| | 2901 TUXEDO AV |
| | CONT: E.O. KOCH CONSTRUCTION |
| | TEL: (863) 385-8649 |
| | |
| | SBC= 1997 STANSARD BUILDING CODE |
| | SBC*= AMENDMENTS STANDARD BUILDING CODE |
| | |
| | TYPE IV BUILD, UNPROTECTED MODEL:LRFM1 |
| | ****** |
| | AMERICAN BUILDING CO. PRODUCT APPROVAL |
| | REPORT LISTED FOR SBCCI # 8966.12 NO |
| | LONGER IS A CURRENT REPORT. SBCCI DOES |
| | SHOW THIS COMPANY WITH A CURRENT REPORT |
| | # 94100 WHICH DOES HAVE PORTIONS USED |
| | FROM THE PREVIOUS ACCEPTED REPORT. |
| | ****** |
| | THIS BUILDING IS LOCATED IN A DESIGNATED |
| | "FIRE DISTRICT". |
| | |
| | F102.2.6: EXTERIOR WALLS OF TYPE IV |
| | BUILDINGS SHALL HAVE A FIRE RESISTANCE |
| | OF 2 HRS OR MORE WHEN SUCH WALLS ARE |
| | LOCATED WITHIN 30' OF A COMMON PROPERTY |
| | LINE OR AN ASSUMED PROPERTY LINE |
| | BETWEEN 2 BUILDINGS/ SAME LOT. |
| | |
| | SBC FIGURE 1606 BASIC WIND SPEEDS, IN- |
| | DICATES THAT THIS BUILDING REQUIRES |
| | A DESIGN FOR 110MPH WIND ZONE. THE SBCCI |
| | TEST: |
| | WIND LOAD: MAXIMUM WIND SPEED 100 MPH. |
| | |
| | SBC104.2.2* ADDITIONAL INFORMATION |
| | REQUIRED, THIS STRUCTURE IS TO BE USED |
| | FOR STORAGE, WHAT TYPE OF MATERIALS ARE |
| | GOING TO BE STORED? PLANS INDICATE POSS- |
| | IBLE ENCLOSED PARKING SEE 411.4. |
| | THE SITE PLAN SHOWS A NATURAL GAS TANK |
| | NEXT TO THE BUILDING, IS THIS A ABOVE |
| | THE GROUND TANK? AMOUNT OF GALLONS? |
| | SBC 404.2.3- 404.2.7 ADDRESS PUMPS AND |
| | OTHER DISPENSING DEVISES. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561)659-8096 X 8412 |