2002-04-05 00:00:00************** PROVISO/REVISION ********
  
 1)NOTE: PLEASE NOTE LOAD CALCULATIONS
 NEED TO MEET ART 220 OF THE NEC.
 PLEASE NOTE THAT PANEL SCHEDULE "B" IS
 SHOWING LOAD FOR PANEL "C" AT 4800VA.
 PLEASE NOTE THE PANEL "C`S" LOAD IS
 SHOWN AT 19,800VA?? PLEASE CORRELATE.
  
 PLEASE REVISE LOAD CALCULATIONS AND
 SUBMIT REVISED PLAN FOR REVIEW BEFORE
 ROUGH ELECTRICAL INSPECTION IS CALLED IN
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  