Plan Review Notes
Plan Review Notes For Permit 01120670
Permit Number 01120670
Review Stop R
Sequence Number 2
Notes
Date Text
2002-03-18 00:00:00*************BUILDING UNSAT*************
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE DESIGN CERTIFICATION FORM FOR
 BUILDING CODE COMPLIANCE REQUIRES THE
 EMBOSSED SEAL OF THE DESIGNER OF RECORD
 IN ADDITION TO THEIR WET SIGNATURE AND
 THE DATE SIGNED. ON FUTURE SUBMITTALS
 PROVIDE THIS INFORMATION ON THE PLANS.
  
 3) PROVIDE ONE COPY OF ENERGY FORM
 600-A WITH ORIGNAL SIGNATURES AS
 REQUIRED FOR PUBLIC RECORD.
 THE FORM ONLY LISTS 3 A/C SYSTEMS AND
 THE PLANS INDICATE 5 SYSTEMS. PLEASE
 CORRECT.
  
 4) PROVIDE LISTING INFORMATION FOR BBQ
 AT COVERED PORCH.
  
 5) PROVIDE CITY OF WPB SITE SPECIFIC
 PRODUCT APPROVAL FORM AND ENGINEERED
 DRAWINGS FOR BUTT GLASS WINDOWS.THE FORM
 IS REQUIRED TO BE SIGNED, SEALED AND
 DATED BY THE ENGINEER AND THE DESIGNER
 OF RECORD.
  
 6)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - AWNING WINDOWS
 - FRONT DOOR WITH SIDELITES (UNLESS THIS
 WILL BE FRENCH DOORS WHICH WOULD BE
 COVERED UNDER THEPRODUCT APPROVAL THAT
 WAS SUBMITTED)
 - GARAGE DOORS (THE CURRENT SBCCI REPORT
 IS #9606C, REPORT AND DRAWINGS ARE
 REQUIRED) ONLY ONE PAGE OF DRAWING 9606
 WAS SUBMITTED.
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202