| 2002-03-01 00:00:00 | *************** UNSAT ***************** |
| | |
| | PLEASE NOTE THAT NOT ALL NOTES FROM |
| | FIRST REVIEW WERE ADDRESSED. |
| | THERE ARE SOME NOTES DUE TO OTHER |
| | CHANGES MADE. |
| | |
| | 1)NOTE: PLEASE NOTE THAT ON FIRST |
| | REVIEW LOAD EXCEEDED PANEL "B" (200A) |
| | AND NOW PANEL WAS INCREASED TO 250A. |
| | PLEASE NOTE CONDUCTORS ARE STILL SHOWN |
| | AT 3/0`S. PLEASE SEE 310-15(B)(6) FOR |
| | SIZING. |
| | |
| | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | NONE WERE SUBMITTED. |
| | |
| | 3)NOTE: PLEASE NOTE THAT SOME LOADS/ |
| | BKRS/AND OCP STILL DO NOT CORRELATE. |
| | PLEASE NOT SOME LOADS EXCEEDRATINGS OF |
| | BRKRS/WIRE. |
| | |
| | 4)NOTE: PLEASE NOTE PLANS ARE SHWOING |
| | EQUIPMENT GROUNDINGCONDUCTORS BETWEEN |
| | GUTTER AND MAIN DISC`S? PLEASE NOTE |
| | THAT THIS IS PARALLELING THE NEUTRAL? |
| | PLEASE NOTE THAT AN EQUIPMENT GROUND IS |
| | ONLY INSTALLED AFTER THE FIRST MEANS |
| | OF DISCONNECT. |
| | |
| | 5)NOTE: PLEASE CLARIFY PLANS SHOWING |
| | A 1/0 BOND?? INSTALLED BETWEEN METER |
| | AND MAIN GUTTER? PLEASE CLARIFY THAT |
| | SERVICE IS SINGLE PHASE AND ALREADY |
| | SHOWS 2 HOTS AND A NEUTRAL?? |
| | |
| | 6)NOTE: PLEASE NOTE MISSING BLDG/FOOTER |
| | STEEL PER 250-50 |
| | |
| | 7)NOTE: PLEASE NOTE STILL MISSING SOME |
| | OUTLETS PER 210-52. SEE SECOND FLOOR |
| | OPEN AREA AND BR#4. |
| | |
| | 8)NOTE: PLEASE NOTE PLANS ONLY SHOW ONE |
| | MAIN DISC NEXT TO METER? PLEASE SHOW |
| | BOTH. GROUPED PER 230-72 |
| | |
| | 9)NOTE: PLEASE CLARIFY WHAT APPEARS TO |
| | BE A A/C CU OUTSIDE CABANA BATH? |
| | PLEASE NOTE THAT IF HEAT PUMP,/ CLARIFY |
| | HEAT PUMP AS IT IS SHOWN AT ONLY AT 2P- |
| | 20A. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |