Plan Review Notes
Plan Review Notes For Permit 01120670
Permit Number 01120670
Review Stop R
Sequence Number 1
Notes
Date Text
2002-01-31 00:00:00*************BUILDING DENIED************
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) PROVIDE ENERGY CALCULATIONS
 AS REQUIRED BY THE 1997 FLORIDA ENERGY
 EFFICIENCY CODE FOR BUILDING
 CONSTRUCTION.
  
 4)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - ROOF TILE (EXPIRED 6-25-01)
 - MULLIONS (EXPIRED 4-9-01)
 - FRENCH DOORS (EXPIRED 11-22-01)
 - GARAGE DOORS (NEED COMPLETE REPORT FOR
 BOTH SIZES OF GARAGE DOORS USED)
 - STORM PANELS FOR ANY GLAZED OPENINGS
 NOT OF IMPACT RESISTANT GLASS
 - SLIDING GLASS DOORS
 - AWNING WINDOWS
 - FRONT DOOR (DOUBLE DOORS W/SIDELITES)
 - CASEMENT WINDOWS
  
 5) INDICATE ATTIC ACCESS ON SECOND FLOOR
 PER 2309.6.
  
 6) PROVIDE LISTING INFORMATION FOR BBQ
 ON COVERED PORCH.
  
 7) PROVIDE CITY OF WEST PALM BEACH SITE
 SPECIFIC ENGINEERING FORM AND ENGINEERED
 DRAWINGS FOR BUTT GLASS WINDOWS. FORM
 MUST BE SIGNED AND SEALED BY THE
 ENGINEER AND THE ARCHITECT.
  
 8) THE GUARDRAIL DETAIL ON A-3 SHOWS
 INCORRECT SPACING FOR INTERMEDIATE RAILS
 CODE STATES THAT A 4" SPHERE SHALL NOT
 PASS BETWEEN THEM PER 1015.3.
  
 9) PROVIDE SAFETY GLASS IN BATHROOMS PER
 2405.2.1.
  
 10) NOTES ON HANDRAILS/GUARDRAILS ON A-3
 CONTAIN INCORRECT INFORMATION. SEE
 CORRECTIONS ON PLAN.
  
 11) THE SOIL REPORT STATES THAT BOTTOM
 OF FOOTERS SHOULD BE A MINIMUM OF 18"
 BELOW ADJACENT GRADE AND CITY AMENDMENTS
 REQUIRE THE FLOOR ELEVATION AT HABITABLE
 AREAS TO BE A MINIMUM OF 4" ABOVE FINISH
 GRADE. THEREFORE, THE EXTERIOR FOOTERS
 MUST BE A MINIMUM OF 22" THICK. PLEASE
 CORRECT.
  
 12) ONE PAIR OF THE PEDESTALS IN THE
 GARAGE DO NOT SHOW THE TWO 4FT. #5 BARS
 INDICATED AT THE OTHER PEDESTALS.
  
 13) THE WALL SECTION ON A-8 DIFFERS ON
 LEDGER ATTACHMENT WITH DETAIL H AND THE
 LEDGER SCHEDULE.
  
 14) STUCCO INFO ON A-8 WALL SECTION IS
 INCORRECT 3 COATS TOTALING 7/8" IS
 REQUIRED, SEE 2504.2.1 AND ASTM C 926.
  
 15) DETAIL J/A-8 LISTED ON SHEET A-7 IS
 NOT INDICATED ON SHEET A-8.
  
 16) PROVIDE A DETAILED WALL SECTION OF
 THE 2X6 EXTERIOR WALL AT SECOND FLOOR
 INDICATING SPECIFIC ANCHORS USED TO
 CONNECT WALL TO FLOOR AND ROOF GIRDERS.
  
 17) REVIEW THE GARAGE DOOR BUCKS ON A-8,
 THE ANCHORS SHOULD EMBED INTO FILLED
 CELL CONCRETE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202