Plan Review Notes
Plan Review Notes For Permit 01120670
Permit Number 01120670
Review Stop E
Sequence Number 1
Notes
Date Text
2002-01-02 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 3) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
 ONLY A FEW LOCATIONS.
  
 4)NOTE: PLEASE NOTE THAT THERE ARE MANY
 LOCATIONS ON PANEL SCHEDULES WHERE THE
 WIRE SIZE/BRKR/ AND LOADS DO NOT
 CORRELATE.
 PLEASE NOTE THAT SOME LOADS EXCEED WIRE
 AND BRKR RATING, SOME OCP IS SHOWN AT
 60A FOR 5KW LOAD?
  
 5)NOTE: PLEASE NOTE PLANS ARE SHOWING
 A WASHER AND DRYER UPSTAIRS ALSO, BUT
 DO NOT SHOW ANY INFORMATION ON PANEL
 SCHEDULES? PLEASE CLARIFY.
  
 6)NOTE: PLEASE NOTE THAT LOAD CALCULATIO
 NS SEEM TO HAVE BEEN MISPRINTED. PLEASE
 NOTE THAT SHOWS VOLTAGE AS 140 INSTEAD
 OF 240 AND SHOWS AMPS INSTEAD OF VOLTS
 PLEASE CORRECT.
  
 7)NOTE: PLEASE NOTE THAT WIRE SIZE FOR
 MAIN SERICE IS NOT LARGE ENOUGH.
 PLEASE NOTE THAT 350MCM IS ONLY RATED
 FOR A 350A SERVICE. 310-15
 PLEASE NOTE LOAD SHOWN EXCEEDS 350AMPS.
 PLEASE CORRECT.
  
 8)NOTE: PLEASE NOTE THAT THE LOAD SHOWN
 FOR PANEL "B" EXCEEDS THE RATING OF
 THE 200A DISCONNECT FEEDING PANEL "B"
 PLEASE CORRELATE.
  
 9)NOTE: PLEASE NOTE MISSING LIGHTING AND
 RECEPT PER 210-70/210-63 FOR AHU IN
 ATTICS/ATTIC ACCESS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372