| 2002-01-02 00:00:00 | ***************** UNSAT *************** |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 2) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S) PER 210-11-C-3. |
| | MUST BE 20A AND #12AWG. |
| | |
| | 3) NOTE: PLEASE SHOW ALL OUTLET SPACING |
| | TO MEET 2`,6`,12` RULE PER 210-52. |
| | ONLY A FEW LOCATIONS. |
| | |
| | 4)NOTE: PLEASE NOTE THAT THERE ARE MANY |
| | LOCATIONS ON PANEL SCHEDULES WHERE THE |
| | WIRE SIZE/BRKR/ AND LOADS DO NOT |
| | CORRELATE. |
| | PLEASE NOTE THAT SOME LOADS EXCEED WIRE |
| | AND BRKR RATING, SOME OCP IS SHOWN AT |
| | 60A FOR 5KW LOAD? |
| | |
| | 5)NOTE: PLEASE NOTE PLANS ARE SHOWING |
| | A WASHER AND DRYER UPSTAIRS ALSO, BUT |
| | DO NOT SHOW ANY INFORMATION ON PANEL |
| | SCHEDULES? PLEASE CLARIFY. |
| | |
| | 6)NOTE: PLEASE NOTE THAT LOAD CALCULATIO |
| | NS SEEM TO HAVE BEEN MISPRINTED. PLEASE |
| | NOTE THAT SHOWS VOLTAGE AS 140 INSTEAD |
| | OF 240 AND SHOWS AMPS INSTEAD OF VOLTS |
| | PLEASE CORRECT. |
| | |
| | 7)NOTE: PLEASE NOTE THAT WIRE SIZE FOR |
| | MAIN SERICE IS NOT LARGE ENOUGH. |
| | PLEASE NOTE THAT 350MCM IS ONLY RATED |
| | FOR A 350A SERVICE. 310-15 |
| | PLEASE NOTE LOAD SHOWN EXCEEDS 350AMPS. |
| | PLEASE CORRECT. |
| | |
| | 8)NOTE: PLEASE NOTE THAT THE LOAD SHOWN |
| | FOR PANEL "B" EXCEEDS THE RATING OF |
| | THE 200A DISCONNECT FEEDING PANEL "B" |
| | PLEASE CORRELATE. |
| | |
| | 9)NOTE: PLEASE NOTE MISSING LIGHTING AND |
| | RECEPT PER 210-70/210-63 FOR AHU IN |
| | ATTICS/ATTIC ACCESS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |