Plan Review Notes
Plan Review Notes For Permit 01120633
Permit Number 01120633
Review Stop ENG
Sequence Number 1
Notes
Date Text
2001-12-24 00:00:00FAILED:
 1. PLEASE PROVIDE STORM WATER
 CALCULATIONS FOR OUR REVIEW AND APPROVAL
 2. PLEASE STATE THAT, WHY THERE ARE TWO
 DETAILS SHOWN FOR EXFILTRATION TRENCH,
 SHEET 3 OF 4 AND 4 OF 4.
 3. IS THERE ANY NEW CONNECTIONS TO THE
 CITY'S WATER AND SEWER.IF SO, BACKFLOW
 PREVENTERS AND CLEAN-OUT MUST BE SHOWN.
 ALSO PLANS FOR SUCH CONNECTIONS MUST BE
 SUBMITTED TO PUBLIC UTILITIES FOR THIER
 REVIEW AND APPROVAL, 659-8040.
 4. CONCRETE TURNOUTS MUST BE AT MIN. PER
 CITY'S STANDARD. SEE ATTACHED.
 5. AT MIN. 12" SUBGRADE MUST BE PROVIDED
 6. ALL OFF- STREET PARKING STALLS MUST
 BE PAINTED WITH DOUBLE 4" WHITE AND BLUE
 FOR H.C.
 7. A SEPARATE PERMIT APPLICATION FOR
 SITE/UNDRGROUND UTILITIES WORKS IS
 REQUIRED.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI