| Plan Review Notes For Permit 01120616 |
| Permit Number |
01120616 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-01-16 00:00:00 | 1) NO FIRE SPRINKLER DRAWINGS PROVIDED | | | WITH PLANS. | | | 2) WITH REGARDS TO FUEL TANK, THE | | | FOLLOWING DETAILS ARE TO BE PROVIDED: | | | A) SIZE OF TANK | | | B) AGE OF TANK | | | C) ANY CERTIFICATIONS ON THE TANK | | | D) TYPE OF PRODUCT STORED IN THE TANK. | | | E) DISTANCES FROM THE BUILDING AND | | | ANY PROPERTY LINES. | | | F) BOLLARD PROTECTION FROM MECHANICAL | | | INJURY. | | | G) VENTING OF TANK. | | | H) LABELING ON THE TANK. | | | THIS INSTALLATION WILL REQUIRE A | | | SEPARATE PERMIT SINCE IT IS A FUEL | | | INSTALLATION. |
|