| Plan Review Notes For Permit 01120614 |
| Permit Number |
01120614 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-01-09 00:00:00 | AS NOTED ON THE PREVIOUS PLAN REVIEW, | | | THIS BUILDING/STRUCTURE IS PART OF THE | | | REGIONAL WATER SUPPLY SYSTEM AND AS | | | SUCH IS DEEMED AN ESSENTIAL FACILITY | | | AND BE DESIGNATED A CATEGORY IV | | | STRUCTURE.SEE ASCE 7-95 SECTION 1.5. | | | | | | SHEET AS-6.IF THE OVERHEAD CRANE IS TO | | | BE SUPPORTED BY THE STRUCTURE THAN | | | COMPLIANCE WITH SBC 1604.7 MUST BE | | | DEMONSTRATED. | | | | | | THE PLANS IN VARIOUS PLACES MAKE | | | REFERENCE TO "SPECIFICATIONS" THAT ARE | | | NOT INCLUDED WITH THE PERMIT | | | APPLICATION.THIS WAS NOTED ON THE | | | FIRST PLAN REVIEW.SBC104.1.3 STATES | | | IN EFFECT THAT THE WORK AUTHORIZED BY | | | THE PERMIT IS THAT WHICH IS DEPICTED ON | | | PLANS AND SPECIFICATIONS WITH THE | | | PERMIT APPLICATION.SEPARATE PERMITS | | | WILL BE REQUIRED FOR "REFERENCED" WORK. |
|