| 2001-12-19 00:00:00 | ****************** UNSAT *************** | | | | | | | | | 1)NOTE: PLEASE CLARIFY A MAIN DISCONNECT | | | AND A MCB PANEL SHOWN AT CABANA? | | | | | | 2)NOTE: PLEASE CLARIFY GROUNDING FROM | | | MAIN PANEL TO DETACHED STRUCTURE PER | | | 250-32. | | | | | | 3)NOTE: PLEASE NOTE 50KW SHOWN FOR | | | CABANA ON MAIN PANEL SCHEDULE. MUST BE | | | A MISPRINT. PLEASE CORRECT | | | | | | 4)NOTE: PLEASE CLARIFY #4 INTO A 2P50 | | | BRKR. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|