Plan Review Notes
Plan Review Notes For Permit 01120445
Permit Number 01120445
Review Stop B
Sequence Number 1
Notes
Date Text
2002-01-07 00:00:00CHECKLIST:
 1-BRING DRAWINGS TO PALM BEACH COUNTY TO
 CONFIRM IF IMPACT FEES ARE DUE OR NOT.
 BRING BACK STAMPED DRAWINGS AND PAID
 RECEIPT.
 2-CLARIFY NEW CONCRETE EDGE CONSTRUCT'N:
 A)HOW IS NEW CONCRETE EDGE ATTACHED TO
 EXISTING CONCRETE SLAB?.
 B)HOW CAN YOU HAVE 9" OF COMPACTED FILL
 BETWEEN EXIST'G CONC. SLAB & NEW SLAB?
 -HOW IS IT COMPACTED? HOW IS NEW SLAB
 FORMED? IS IT GOOD IDEA TO HAVE FILL
 IN BETWEEN TWO SLABS? PROVIDE MORE
 INFORMATION AS REQUIRED TO CLARIFY.
 C)CLARIFY INSTALLATION OF NEW BOTTOM AND
 TOP WOOD PLATES. ARE THEY CONTINUOUS
 OR THEY WILL BE STOPPED AT EA. EXIST'G
 STUD? WHAT ABOUT THE EXISTING STUDS?
 ARE THEY GOING TO BE BURIED BY NEW
 CONCRETE EDGE? HOW ARE THEY GOING TO
 BE ISOLATED FROM THE CONCRETE?
 3-SPECIFY FIREBLOCKING AT CONCEALED
 SPACES. SEE SEC. 2305 SBC 1997.
 4-PROVIDE COMPLETE FRAMING DETAILS FOR
 ROUND WINDOW AND EXTERIOR FRENCH DOORS
 SPECIFY ALL FASTENERS. SECTION 104.2.2
 CITY AMENDMENTS TO SBC 1997.
 5-CLARIFY WHICH GLAZING AREAS ARE GOING
 TO HAVE STORM SHUTTERS OR MISSILE
 IMPACT GLAZING. PRODUCT APPROVALS
 SUBMITTED ARE FOR BOTH.
 -IF STORM SHUTTERS ARE USED, THEN
 SPECIFY ON PRODUCT APPROVAL SPECIFIC
 MOUNTING CONDITIONS AND ANCHOR AND
 SPACING TO BE USED ACCORDING TO THE
 STRUCTURE TO BE ATTACHED TO. ALSO,
 PROVIDE A KEY PLAN AND INSTALLATION
 SCHEDULE. SEE CITY SAMPLE ATTACHED.
 6-PROVIDE LEGIBLE PRODUCT APPROVAL FOR:
 A)FLAT ROOF SYSTEM TO BE USED.
 B)ROUND WINDOW. PRODUCT APPROVAL GIVEN
 IS FOR RECTANGULAR WINDOWS, NOT ROUND
 WINDOWS. SEE APPROVED DRAWINGS.
 C)STORM SHUTTERS WITH LEGIBLE DRAWINGS
 IS STORM SHUTTERS WILL BE USED.
 7-OWES $101.00 FOR UPDATED VALUATION.
 PLEASE PAID ATTACHED RECEIPT AND BRING
 BACK PAID RECEIPT.
 8-NEED TO PROVIDE ONE HOUR FIRE RATED
 WALL AT NORTH AND WEST SIDE OF BLDG.
 AS REQUIRED BY TABLE 600 SBC 1997.
 9-PROVIDE UPLIFT CALCULATIONS FOR ROOF
 TRUSSES AND SPECIFY HURRICANE ANCHORS
 AS REQUIRED.
 10-REVISE ENERGY CALCULATIONS:
 -IF THERE IS A WINDOW UNIT HOW COME
 THERE IS A DUCTWORK WITH R-6 INSULAT'N
 -ITEM #13 APPLIES TO MANUFACTURED HOMES
 ONLY. SEE NOTE WITH ASTERISK.