| Plan Review Notes For Permit 01120366 |
| Permit Number |
01120366 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-01-12 00:00:00 | APPROVED WITH PROVISO: | | | 1-FLOD ZONE A8. WILL NEED TO PROVIDE THE | | | ELEVATION CERTIFICATE. | | | | | | 2-RESUBMIT STORM PANELS PRODUCT APPROVAL | | | DRAWINGS SUBMITTED ARE VALID FOR ONE | | | PERMIT ONLY. SEE NOTE ON STORM SHUTTER | | | DRAWINGS. | | | 3-PROVIDE UPDATED PRODUCT APPROVAL FOR | | | ENTRY DOOR. | | | 4-REVISE DETAIL AND SPECIFICATIONS FOR | | | CEILING INSTALLATION AT ENTRY AND REAR | | | PORCHES. SEE ASTM C926 AND ASTM C1063. | | | REVISE ORIGINAL DRAWING TO AVOID | | | FUTURE DELAYS OR FIELD CONFLICTS. | | | 5-SUBMIT CURRENT PRODUCT APPROVAL FOR | | | GARAGE DOOR. PRODUCT APPROVAL THAT | | | WAS SUBMITTED WAS DELETED BY SBCCI. | | | 6-CLARIFY ROOF SHEATHING FASTENING: | | | WALL SECTION ON DRAWING A2 SAYS ONE | | | THING AND STRUCTURAL NOTES ON DRAWING | | | A4 SAYS ANOTHER. REVISE AS REQUIRED. | | | 7-PROVIDE PRODUCT APPROVAL FOR ONE HOUR | | | FIRE RATED GLASS BLOCK OR DELETE | | | OPTION FROM DRAWINGS. |
|