| 2001-12-31 00:00:00 | ***************** UNSAT************** | | | | | | 1)NOTE: PLEASE NOTE ELECTRICAL PANEL | | | "A" SHOWS MCB AND PANEL SCHEDULE SHOW | | | MLO?, PLEASE NOTE PANEL"A" IS SHOWN | | | COMING FROM METER AND NOT THE 200A RT | | | PANEL, PLEASE CORRECT. | | | | | | 2)NOTE: PLEASE CLARIFY MISSING DOOR | | | UPSTAIRS BEDROOM? | | | | | | 3)NOTE: PLEASE NOTE A EXTRA SD NEEDS TO | | | BE INSTALLED IN HALLWAY UPSTAIRS OR | | | MOVE ONE SHOWN AROUND CORNER. NFPA-72 | | | 2-2.1.1.1 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|