| Plan Review Notes For Permit 01120360 |
| Permit Number |
01120360 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-01-11 00:00:00 | ************BUILDING PROVISO************ | | | | | | 1) STRUCTURE IS LOCATED IN AN A8 FLOOD | | | ZONE. AN ELEVATION CERTIFICATE IS | | | REQUIRED. | | | | | | 2) RESUBMIT STORM PANEL INFORMATION WITH | | | MASTERED DRAWINGS. THE ONES SUBMITTED | | | ARE COPIES OF ENGINEERED DRAWINGS THAT | | | WERE VALID ONLY FOR ONE TIME PERMIT, AS | | | STAMPED ON THE DRAWINGS. | | | | | | 3) REVISE TYPICAL EXTERIOR CEILING | | | DETAIL TO COMPLY WITH ASTM C-1063, WHICH | | | REQUIRES 1-3/4" PENETRATION INTO | | | HORIZONTAL WOOD FRAMING MEMBERS BY | | | FASTENERS. (2" STAPLES) |
|