| Plan Review Notes For Permit 01120358 |
| Permit Number |
01120358 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-01-28 00:00:00 | ************BUILDING PROVISO************ | | | | | | 1) STRUCTURE IS LOCATED IN AN A8 FLOOD | | | ZONE, AN ELEVATION CERTIFICATE IS | | | REQUIRED. | | | | | | 2) RESUBMIT STORM PANEL INFORMATION WITH | | | MASTERED DRAWINGS. THE ONES SUBMITTED | | | WERE VALID FOR ONE PERMIT ONLY. | | | | | | 3) SUBMIT CURRENT PRODUCT APPROVAL FOR | | | GARAGE DOOR. SBCCI HAS DELETED THE 2015 | | | REPORT FOR ABLE GARAGE DOORS. | | | | | | 4)CORRECT THE EXTERIOR CEILING DETAIL ON | | | A-1 & A-1B TO COMPLY WITH ASTM C- 1063, | | | WHICH REQUIRES FASTENERS TO PENETRATE | | | INTO HORIZONTAL FRAMING 1-3/4", ON | | | FUTURE SUBMITTALS. | | | | | | 5) THE MASTER BEDROOM WINDOWS MUST MEET | | | THE EGRESS REQUIREMENTS OF 97 SBC 1005.4 |
|