| Plan Review Notes For Permit 01120356 |
| Permit Number |
01120356 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-01-17 00:00:00 | ************BUILDING PROVISO************ | | | | | | 1) STRUCTURE IS LOCATED IN AN A8 FLOOD | | | ZONE,AN ELEVATION CERTIFICATE IS | | | REQUIRED. | | | | | | 2) RESUBMIT STORM PANEL INFORMATION WITH | | | MASTERED DRAWINGS. THE ONES SUBMITTED | | | WERE VALID FOR ONE PERMIT ONLY. | | | | | | 3) PROVIDE UPDATED PRODUCT APPROVALS FOR | | | FRONT DOOR. | | | | | | 4) SUBMIT CURRENT PRODUCT APPROVALS FOR | | | GARAGE DOOR. SBCCI HAS DELETED THE 2015 | | | PRODUCT EVALUATION REPORT. | | | | | | 5) REVISE THE EXTERIOR CEILING DETAIL ON | | | A-1 & A-1B TO COMPLY WITH ASTM C-1063, | | | WHICH REQUIRES FASTENERS TO PENETRATE | | | 1-3/4" INTO HORIZONTAL FRAMING MEMBERS. | | | | | | 6) MSATER BEDROOM WINDOWS MUST COMPLY | | | WITH 97 SBC 1005.4, FOR EMERGENCY | | | ESCAPE AND RESCUE OPENINGS. |
|