| Notes |
| Date |
Text |
| 2002-02-02 00:00:00 | DENIED | | | REFERENCE: SPC-94-FACBC-97 | | | | | | 1) SHT A-1 SHOW CLEAR FLOOR SPACE AND | | | TURNING RADIUS FOR TOILET ROOM. | | | 2) SHT A-1 MINIMUM FIXTURES REQUIREMENTS | | | SPC TABLE 407 REQUIRE A DRINKING FOUNT- | | | AIN. | | | 3) SHT A-1 SANT RISER DIAGRAM, MOP SINK | | | NOT SHOWN. | | | 4) SHT A-1 WATER RISER DIAGRAM, PLEASE | | | LOCATE WATER HAMMER ARRESTORS NEAR FIX- | | | TURES IN "EFFECTIVE RANGE" NOT AT TOP OF | | | DROP AS SHOWN PER PDI-WH 201 AND MANUF. | | | INSTALLATION INSTRUCTIONS. | | | 5) BACKFLOW REQUIRED ON WATER SERVICE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|