| Plan Review Notes For Permit 01120298 |
| Permit Number |
01120298 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-01-31 00:00:00 | *******************DENIED*************** | | | | | | | | | COMMENT #2 FROM REVIEW DATED 12-18-0 WAS | | | NOT ADDRESSED. | | | | | | PROVIDE DETAIL OF EXHAUST TERMINATION. | | | AS PER NFPA 33 AIR EXHAUSTED SHALL BE | | | CONDUCTED BY DUCTS DIRECTLY TO THE | | | OUTSIDE OF THE BUILDING BY THE MOST | | | DIRECT ROUTE TO THE POINT OF DISCHARGE. | | | (SHALL NOT PENETRATE FIRE WALL)THE | | | EXHAUST DUCT DISCHARGE SHALL BE AT | | | LEAST 6 FT FROM ANY EXTERIOR WALL OR | | | ROOF.DUCT SHALL NOT DISCHARGE IN THE | | | DIRECTION OF ANY COMBUSTIBLE | | | CONSTRUCTION THAT IS WITHIN 25 FT OF | | | THE EXHAUST DISCHARGE POINT NOR SHALL | | | IT DISCHARGE IN THE DIRECTIONS OF ANY | | | UNPROTECTED IN NONCOMBUSTIBLE OR | | | LIMITED COMBUSTIBLE CONSTRUCTIONS THAT | | | IS WITHIN 25 FT OF THE EXHAUST | | | DISCHARGE POINT. | | | | | | INDICATE ON PLAN HOW EXHAUST DUCT | | | TERMINATION WILL BE SECURED TO THE ROOF. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|