| Date |
Text |
| 2001-12-18 00:00:00 | *******************DENIED*************** |
| | |
| | PLEASE PROVIDE ADDITIONAL MANUFACTURER |
| | INSTALLATION INSTRUCTIONS FOR THE |
| | MODULAR OFFICE.INDICATE WHAT TYPE OF |
| | AC SYSTEM IS BEING INSTALLED WITH THIS |
| | MODULAR OFFICE SPACE. |
| | |
| | ADDITIONAL PLANS AND PERMIT REQUIRED FOR |
| | THE SPRAY BOOTH.PROVIDE THE FOLLOWING |
| | INFORMATION FOR REVIEW WITH PERMIT |
| | APPLICATION. |
| | |
| | 1.INDICATE WHAT TYPE OF APPLICATION IS |
| | BEING DONE IN THE SPRAY BOOTH. |
| | |
| | 2.INDICATE LOCATION/TERMINATION OF |
| | EXHAUST TO SPARY BOOTH. PLEASE NOTE |
| | AS PER 1997 SMC 506.1, EXHAUST OUT- |
| | LETS FOR DUCTS CONVEYING NOXIOUS |
| | GASES, FLAMMABLE VAPORS & CORROSIVE |
| | VAPORS, SHALL TERMINATE OUTSIDE THE |
| | BUILDING & SHALL BE LOCATED 10 FT |
| | FROM ANY ADJACENT BUILDING, PARKING |
| | AREA, PROPERTY LINE, WINDOW, DOOR, |
| | OR AIR INTAKE AND 10 FT ABOVE THE |
| | ADJOINING GRADE LEVEL.SHOULD |
| | EXHAUST TERMINATE ABOVE THE ROOF IT |
| | SHALL BE A MINIMUM OF 40" ABOVE THE |
| | ROOF SURFACE. |
| | |
| | PLEASE SEE FIRE DEPT COMMENTS FOR |
| | ADDITIONAL INFORMATION REQUIRED. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT 659-8096 |
| | EXT 8388. |