| Date |
Text |
| 2001-12-11 00:00:00 | 1) WHAT WILL THE SPRAY BOOTH BE USED |
| | FOR. |
| | 2) THE SPRAY BOOTH REQUIRES A FIRE |
| | SUPPRESSION SYSTEM. SEPARATE PLANS AND |
| | PERMITS REQUIRED FOR SPRAY BOOTH. |
| | 3) THE SPRAY BOOTH REQUIRES THREE FEET |
| | AROUND IT FOR CLEANING PURPOSES. |
| | 4) THE SPRAY BOOTH REQUIRES GROUNDING. |
| | 5) IF THE SPRAY BOOTH IS USED TO SPRAY |
| | FLAMMABLE OR COMBUSTIBLE LIQUIDS, WHERE |
| | WILL THESE ITEMS BE STORED WHEN NOT |
| | BEING SPRAYED. |
| | 6) PLEASE DEMONSTRATE COMPLIANCE WITH |
| | THE STANDARD MECHANICAL CODE, SECTION |
| | 506.1 WHICH REQUIRES THE EXHAUST DUCT |
| | TO BE AT LEAST 10 FEET FROM THE |
| | BUILDING, ADJACENT BUILDINGS, |
| | PROPERTIES, PARKING AREAS, ETC. |
| | 7) NO ELEVATION DRWAINGS OF THE |
| | BUILDING PROVIDED. |
| | 8) PLEASE INDICATE HOW MAKE-UP AIR IS |
| | BEING PROVIDED FOR THE SPRAY BOOTH. |
| | 9) PLEASE INDICATE LOCATIONS OF FIRE |
| | EXTINGUISHERS. |
| | 10) PLEASE INDICATE LOCATIONS OF |
| | WRNING SIGNS ASSOCIATED WITH SPRAY |
| | BOOTH. |
| | 11) ELECTRICAL REQUIREMENTS TO COMPLY |
| | WITH NFPA 33 REQUIREMENTS. |
| | 12) IS THE WALL ADJACENT TO THE SPRAY |
| | BOOTH A DEMISING WALL OR AN EXTERIOR |
| | WALL. |
| | |
| | MIKE CARSILLO, CAPTAIN |
| | 659-8096,EXT.8497 |
| | 835-2910 |