| Plan Review Notes For Permit 01120298 |
| Permit Number |
01120298 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-12-07 00:00:00 | ****************** UNSAT ************** | | | | | | 1)NOTE: PLEASE SHOW LAYOUT AROUND NEW | | | SPRAY BOOTH TO MEET 516. | | | | | | 2)NOTE: PLEASE NOTE MISSING EQUIPMENT | | | GROUNDING CONDUCTORS BETWEEN MAIN PANEL | | | AND PANEL "B". | | | | | | 3)NOTE: PLEASE NOTE MISSING PANEL "B" | | | PANEL SCHEDULE, PANEL "C"??? | | | | | | 4)NOTE: PLEASE CLARFIY 3/0`S FROM 100A | | | OCP SHOWN ON PANEL "A" FEEDING "B". | | | | | | 5)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | | | | 6)NOTE: PLEASE CLARIFY IF ONLY HALF OF | | | THE EXSITING SERVICE WILL BE ELIMINATED? | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|