2001-12-06 00:00:001) IF A FIRE SPRINKLER SYSTEM EXISTS,
 THEN FLOW AND TAMPER SWITCHES ARE TO
 BE CONNECTED TO THE FIRE ALARM SYSTEM.
 2) DUCT SMOKE DETECTORS ARE REQUIRED
 IN HVAC SYSTEMS OVER 2000 CFM. NONE
 ARE SHOWN.
 3) NO DEVICES SHOWN FOR FIRST FLOOR.
 ARE ANY EXISTING DEVICES PRESENT.
 APPROVED PROVISO: