Plan Review Notes
Plan Review Notes For Permit 01120265
Permit Number 01120265
Review Stop P
Sequence Number 1
Notes
Date Text
2002-01-12 00:00:00DENIED;
 1.RISER DIAGRAM NOT TO CODE.
 A.UPSTAIRS BATH (LEFT) SHOWER DRAIN
 UNVENTED.
 B.W/M REQUIRES A TRAP.
 C.UP STAIRS BATH (RIGHT) W/C FLUSH-
 ING PAST UNVENTED SHOWER.
 D.MASTER BATH TUB AND SHOWER ARE NOT
 VENTED.
 E.1/2 BATH AND KITCHEN SINK ARE NOT
 SHOWN ON RISER DIAGRAM.
 F.PIPING SIZING IS NOT CORRECT.
 2.ADDITIONAL PERMIT AND PLANS ARE
 REQUIRED FOR GAS.
 3.SHOW CALKULATIONS FOR LAUNDRY ROOM.
 SEE 97 SGC CHAPTER 2 (CONFINED SPACE)
 FOR EQUATION.IF ROOM IS TOO SMALL SHOW
 VENTS, SIZE AND LOCATION TO COMPLY
 WITH THE 97 SGC.
 PLUMBING PLAN REVIEW BY
 JOHN LEECH
 659-8096 EXT.8369