| Plan Review Notes For Permit 01120265 |
| Permit Number |
01120265 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-01-12 00:00:00 | DENIED; | | | 1.RISER DIAGRAM NOT TO CODE. | | | A.UPSTAIRS BATH (LEFT) SHOWER DRAIN | | | UNVENTED. | | | B.W/M REQUIRES A TRAP. | | | C.UP STAIRS BATH (RIGHT) W/C FLUSH- | | | ING PAST UNVENTED SHOWER. | | | D.MASTER BATH TUB AND SHOWER ARE NOT | | | VENTED. | | | E.1/2 BATH AND KITCHEN SINK ARE NOT | | | SHOWN ON RISER DIAGRAM. | | | F.PIPING SIZING IS NOT CORRECT. | | | 2.ADDITIONAL PERMIT AND PLANS ARE | | | REQUIRED FOR GAS. | | | 3.SHOW CALKULATIONS FOR LAUNDRY ROOM. | | | SEE 97 SGC CHAPTER 2 (CONFINED SPACE) | | | FOR EQUATION.IF ROOM IS TOO SMALL SHOW | | | VENTS, SIZE AND LOCATION TO COMPLY | | | WITH THE 97 SGC. | | | PLUMBING PLAN REVIEW BY | | | JOHN LEECH | | | 659-8096 EXT.8369 |
|