2002-02-01 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01120265
 202 WESTMINISTER RD
 CONT: LEVESQUE CONST
 TEL: 758-1939
  
 SBC= 1997 STANDARD BUILDING CODE
 SBC*= AMENDMENTS/ STANDARD BUILDING CODE
  
  
 1)- DISCREPANCY BETWEEN THE SURVEY WEST
 SETBACK OF 5'-8" ON SURVEY VS 7'-0" ON
 THE PLOT PLAN.
  
 2)- SBC 1606.2.6.2/ PRODUCT APPROVALS:
 A) DOOR # 19 MISSING PRODUCT APPROVAL
 FOR INSWING FRONT DOOR.
 B) DOOR #3 & 4 OVERHEAD GARAGE DOORS,
 PLANS INDICATE THE DOORS TO BE 9'-0"X
 7'-0" THE PRODUCT APPROVAL IS FOR A
 9'-0"X 8'-0" ONLY.
 C) FRENCH DOORS INDICATE A TRANSOM
 ABOVE, THE PRODUCT APPROVALS ARE FOR
 "LIMITATIONS" TESTED FOR A SINGLE
 UNIT. PRODUCT TESTING REPORT FOR
 MULLIONS SHALL BE REQUIRED.
 THE SAME SITUATION EXIST WITH THE
 USE OF MULIPLE WINDOWS, SEE LIMIT-
 ATIONS.
 D) FRENCH DOORS WITH A SIDELITE SHALL
 ALSO BE TESTED IN THIS SAME MANNER.
 SEE LIMITATIONS.
 E) FIXED GLASS PRODUCT LIMITATION
 ONE UNIT SHALL REQUIRE MULLION REPORT
  
 3) SBC 1005.4.4 EMERGENCY ESCAPE & RES-
 CUE OPENINGS:MINIMUM SIZE, CLEAR OPENING
 SEE ATTACHMENT, ALSO 5.7 SQ. FT REQUIRED
 OPEN AREA FOR SLEEPING ROOMS ABOVE THE
 FIRST FLOOR.
  
 4)- FACTORY BUILT FIREPLACES & CHIMNEYS:
 SBC 2806.1.2 FACTORY BUILT FIREPLACES
 SHALL BE TESTED IN ACCORDANCE WITH &
 MEET THE REQUIREMENTS OF UL 127 & SEC.
 2806. SBC 2810 FRESH AIR INTAKE.
  
 5)- SHEET 8 FIREPLACE CHIMNEY FRAMING,
 INDICATE THE SYSTEM TO RESIST MOMENT OF
 OVERTURNING, FRAMING DETAILS, GIRDER
 TRUSS AND ATTACHMENT TO RESIST 110 MPH
 WINDS!
  
 6)- DOOR #20 INTERIOR DOOR INDICATES
 SAME AS 14, A POCKET DOOR, WHILE PLANS
 INDICATE SWING?
  
 7)- SHEET 3 SBC 2309.6 ATTIC ACCESS:
 22'X36", HOUSE & 2ND FLOOR GARAGE.
  
 8)- SHEET 9-4 MISSING POST TO BUILT UP
 BEAM CONNECTION.
  
 9)- TRUSS & GIRDER LOADS,VERTICAL,
 HORIZONTAL & GRAVITY, HURRICANE ANCHOR-
 ING SCHEDULE WITH MANUFAC. LOADS, UPLIFT
 VALUES, PLY, 12 OR 3 TRUSS
  
 10)- GARAGE 2ND STORY OVER 500 SQ FT
 SBC 2305.2.2 DRAFT STOPPING REQUIRED
  
 11)- SHEET 9, SHEET 10 ANCHOR LEDGER
 BOLTS, LENGTH?
  
 12)- SHEET 4&5 GUARDRAILS SEE SECTION
 1015.3 OPENINGS, A 4" SPHERE CAN NOT
 PASS THROUGH PICKETS, BOTTOM RAIL
 A 2" SPHERE CAN NOT PASS BETWEEN THE
 FLOOR AND BOTTOM RAIL.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X8412